The Maxi-Grid 550 Standard Link Panel is the antimicrobial, heavy-duty variant in the linked panel line — pre-linked 3-ply MERV 8 panels with two key upgrades over the standard MG300 Link: the media is treated with an antimicrobial agent to inhibit microbial growth on captured organic matter, and the internal support wire is heavy-duty for maximum frame rigidity in demanding side-access installations. Initial pressure drop is 0.28″ w.g. at 400 FPM per panel with a dust holding capacity of 268 grams at 1.5″ w.g., identical to the MG300 Link.
What link panels are and why they matter
Link panels are pre-linked continuous strips of individual filter panels designed to drop into side-access filter housings as a single unit. Standard panel filters (front-access) install one panel at a time into a holding frame; link panels replace an entire row of filters in one motion. Two operational benefits result:
-
Eliminated air bypass: Conventional individual panels can leave gaps between filters or at the end of a track, allowing unfiltered air to pass through. Link panels are continuously joined — no gaps, no bypass.
-
Faster installation and removal: Maintenance personnel pull and replace one continuous unit per filter track instead of multiple individual panels. Significant labor savings on large air handlers.
Configure the link panel to match your housing length: each Maxi-Grid MG550 Link Panel is built around 12″-tall individual panel sections joined together. Choose the number of panels (2 through 8, or the 24-panel Master Link) based on the length of your housing track, and the panel width (12″x22″, 12″x24″, or 12″x25″) based on your housing depth.
When Maxi-Grid MG550 Link Panel is specified
-
Healthcare and clinical facilities with side-access housings — antimicrobial treatment is a meaningful upgrade for biological-load environments
-
Food processing and hospitality in side-access configurations
-
High-moisture installations — humid and condensing environments where standard panel media might support microbial growth
-
Demanding commercial side-access AHUs — heavy-duty wire support adds rigidity for installations with rough handling or vibration
-
Long-cycle commercial HVAC — antimicrobial protection extends practical service life between changeouts
Sizing the link panel to your housing
Each link panel is identified by two dimensions:
-
Panel count: How many 12″-tall panels are linked end-to-end. Available: 2-panel (12″x44″-46″ total length), 3-panel (66″-69″), 4-panel (88″-92″), 5-panel (110″-115″), 6-panel (132″-138″), 7-panel (154″-161″), 8-panel (176″-184″), or the 24-panel Master Link (continuous extra-long unit). Select the count that matches your housing track length.
-
Panel width: 12″x22″, 12″x24″, or 12″x25″. Match to your housing depth.
Design and construction
-
Configuration: Pre-linked continuous panel filter for side-access housings, 3-ply construction
-
Media: 100% synthetic, progressively dense (suitable for high-moisture applications)
-
Frame: Self-sealing design with steel internal support wire (heavy-duty)
-
Tackifier: Downstream
-
Antimicrobial: Yes (media-side treatment)
-
Efficiency rating: MERV 8 per ASHRAE Test Standard 52.2
-
Initial pressure drop: 0.28″ w.g. at 400 FPM face velocity (per panel)
-
Dust holding capacity: 268 grams at 1.5″ w.g. final pressure drop (per panel)
-
Listings: UL Classified per UL Standard 900
-
Reference bulletin: Koch K-902
What MERV 8 captures
Captures dust mite debris, pollen, mold spores, pet dander, and most household and office airborne dust. The standard residential and commercial efficiency for everyday indoor air quality, balancing capture performance with airflow.
Antimicrobial treatment
The MG550 Link Panel media is treated with an antimicrobial agent that inhibits the growth of bacteria, fungi, and other microorganisms on captured organic matter (dust, skin cells, pollen, etc.). This makes the MG550 a strong choice for installations where captured biological material would otherwise become a substrate for microbial growth over the filter’s service life — healthcare environments, food processing, hospitality, and high-occupancy commercial buildings. The antimicrobial treatment protects the filter media itself; it does not actively kill airborne pathogens passing through the filter.
Choosing across the Maxi-Grid Link Panel line
Koch offers four Maxi-Grid Link Panel sub-lines, each tuned for a different application:
-
MG200 Link (MERV 7): Most economical, 3-ply, downstream tackifier. Equipment protection and side-access prefilter applications.
-
MG300 Link (MERV 8): All-purpose workhorse, 3-ply, lowest pressure drop in the line, encapsulated tackifier. Standard commercial HVAC.
-
MG400 Link (MERV 11): Higher efficiency, 4-ply, higher pressure drop. Light-industrial and high-IAQ commercial.
-
MG550 Link (MERV 8): Antimicrobial-treated 3-ply with heavy-duty wire support. Healthcare, food processing, high-moisture sites.
Link Panels vs. Standard Panels
If your housing uses a front-access design (single panels installed one-by-one into a holding frame), use the standard Maxi-Grid MG550 Panel rather than this link panel. Link panels are purpose-built for side-access housings where the entire continuous unit slides into a track.
Sizing and ordering notes
-
Confirm your housing track length and depth before ordering. Match the panel count to track length and panel width to housing depth.
-
Sold by the case. Carton quantity varies by panel count: 2-panel link = 12 units per case; 3-panel = 8; 4-panel = 6; 5-panel = 5; 6-panel = 4; 7-panel and 8-panel = 3; 24-panel Master Link = 1 per case. The variant price is the case price.
-
Need a non-standard length or width? Request a quote for custom link configurations or facility-scale orders.